- Overview
- Technical data
- Accessories
- Certification
- Business data
- Download
Product advantages
☑ This module adopts 4-channel thermal resistance measurement and supports 13 types of conventional thermal resistors.☑ Supports four way sensors.
☑ Supports 2-wire and 3-wire sensors.
☑ Two LED indicators indicate that the module is operating normally and communication is normal.
☑ Each channel is equipped with LED indicator lights.
☑ Magnetic isolation between the on-site layer and the system layer.
☑ Transmitted in 16 resolution format.
☑ Protection level IP20.
3D model
Technical Information
System feed current | <100mA |
Process alarm | Upper/lower limit of each channel |
Reverse circuit protection | Yes |
Error diagnosis | Yes |
Working voltage | 24V DC+20%/-15% |
Frequency interference suppression | 10Hz | 50Hz | 60Hz | 400Hz |
Sensor type | Thermal resistance |
Temperature error | ± 50ppm/K_ X005f max |
Measuring range | -200 ° C~850 ° C |
Diagnosis | Broken line/parameter assignment error |
Number of channels | 4 |
Data size | 8 Byte |
Resolving power | 16bit, 0.1 ℃/per digit |
Signal type | PT100, PT1000 |
Conversion time | 100-800ms, configurable |
150ms | |
Isolation method | Magnetic isolation from the on-site layer |
Accuracy | ± 0.3% |
Environmental requirements
Protection type | IP20 |
Relative humidity (non condensing) | 5-95% RH |
working temperature | -25... 60 ℃ |
Storage temperature | -40... 85 ℃ |
Wiring parameters
Provide internal system voltage | 5VDC |
The maximum crimping area of the wire | 1.5mm² |
0.14mm² | |
Maximum crimping area of wire (AWG) | AWG16 |
AWG26 | |
Connection technology: input/output | PUSH-IN type terminal blocks |
Installation method | DIN-35 type guide rail |
External dimensions (HXWXD) | 100mm X 48mm X 69mm |
Provide internal system current | Max.2A |
Order number | 30050002406 |
Packing unit | 1 |
Minimum order quantity | 1 |
Products weight (without packaging) | 60g |